HOLIP 變頻器與西門子 S7-200的通訊
TITLE:
// holip變頻器與simens S7-200通訊案例
// 備注:變頻器參數設定:變頻器地址:001;波特率:9600;通訊資料方式:8位元無校驗ASCII碼
// Serial A CD160 = 1;CD161 = 1;CD162 = 0; CD033=2; CD034=2
// Serial C C109=1; C110=1; C111=0; C012=2; C013=2
Network 1 // 設定參數
LD SM0.1
MOVB 9, SMB30 //初始化
LD I0.0
EU
MOVB 17, VB200
MOVB 16#3A, VB201
MOVB 16#1, VB100
MOVB 16#02, VB101
MOVB 16#03, VB102
MOVB 16#0, VB103
MOVB 16#13, VB104
MOVB 16#88, VB105
CALL SBR0
MOVB 16#0D, VB216
MOVB 16#0A, VB217
XMT VB200, 0
Network 2 // 設定串口頻率
LD I0.1
EU
MOVB 15, VB200
MOVB 16#3A, VB201
MOVB 16#1, VB100
MOVB 16#05, VB101
MOVB 16#02, VB102
MOVB 16#0B, VB103
MOVB 16#B8, VB104
MOVB 16#0, VB105
CALL SBR0
MOVB VB214, VB212
MOVB VB215, VB213
MOVB 16#0D, VB214
MOVB 16#0A, VB215
XMT VB200, 0
Network 3 // 變頻器運轉
LD I0.2
EU
MOVB 13, VB200
MOVB 16#3A, VB201
MOVB 16#1, VB100
MOVB 16#03, VB101
MOVB 16#1, VB102
MOVB 16#1, VB103
MOVB 16#0, VB104
MOVB 16#0, VB105
CALL SBR0
MOVB VB214, VB210
MOVB VB215, VB211
MOVB 16#0D, VB212
MOVB 16#0A, VB213
XMT VB200, 0
Network 4 // 變頻器停止
LD I0.3
EU
MOVB 13, VB200
MOVB 16#3A, VB201
MOVB 16#1, VB100
MOVB 16#03, VB101
MOVB 16#1, VB102
MOVB 16#08, VB103
MOVB 16#0, VB104
MOVB 16#0, VB105
CALL SBR0
MOVB VB214, VB210
MOVB VB215, VB211
MOVB 16#0D, VB212
MOVB 16#0A, VB213
XMT VB200, 0
/////////////////////////////
lrc
/////////////////////////////
TITLE
// 子程序:lrc校驗
Network 1 // 網絡題目 (單行)
// LRC校驗
LD SM0.0
MOVW 16#0, AC0
HTA VB100, VB202, 2
HTA VB101, VB204, 2
HTA VB102, VB206, 2
HTA VB103, VB208, 2
HTA VB104, VB210, 2
HTA VB105, VB212, 2
+I VW100, AC0
+I VW101, AC0
+I VW102, AC0
+I VW103, AC0
+I VW104, AC0
+I VW105, AC0
+I VW106, AC0
MOVW AC0, VW110
INVB VB111
//INCB VB111
HTA VB111, VB214, 2
文章版權歸西部工控xbgk所有,未經許可不得轉載。